Explosion-proof Chiller Series
Explosion-proof Air-cooled Chiller and Heat Pump Unit (Screw Type)
Explosion-proof Air-cooled Chiller and Heat Pump Unit (Screw Type)
Application Scenarios

● Hazardous areas with explosive gas mixtures: Zone 1, Zone 2.

● Explosive gas mixtures: IIA, IIB, IIC.

● Hazardous areas with explosive dust: Zone 20, Zone 21, Zone 22.
MESSAGE
PRODUCT DESCRIPTION

Application Scenarios

● Hazardous areas with explosive gas mixtures: Zone 1, Zone 2.

● Explosive gas mixtures: IIA, IIB, IIC.

● Hazardous areas with explosive dust: Zone 20, Zone 21, Zone 22.


Product Features:

1. Utilizes high-quality key components from internationally renowned manufacturers, featuring a carefully designed structure and optimal system configuration.

2. The unit is reliable, durable, energy-efficient, compact, with low noise and vibration, and is easy to operate and maintain. It supports both local and remote control.

3. The heat pump unit integrates cooling and heating functions, capable of providing cooling in summer and heating in winter.

4. The unit does not require a cooling tower or other cooling water systems, making it suitable for areas with limited water resources. It also does not need a dedicated equipment room and can be installed directly outdoors or on rooftops, saving floor space.

5. Incorporates the most advanced explosion-proof technology to ensure superior explosion-proof performance, enabling safe and reliable operation.

6. Widely used in hazardous locations with combustible gases in industries such as military, petroleum, chemical, and pharmaceutical sectors.

Item

BKT-100

BKT-180

BKT-230

Cooling Capacity

100 Kw

180 Kw

230 Kw

Heating Capacity (Heat Pump)

110 Kw

190 Kw

240 Kw

Power Input at Rated Condition

36.8 Kw

66.4 Kw

81.7 Kw

Capacity Control Range

0~50~100%

0~50~100%

0~50~100%

Power Supply

AC380V 3N~ 50Hz

AC380V 3N~ 50Hz

AC380V 3N~ 50Hz

Noise Level

75 dB(A)

77 dB(A)

78 dB(A)

Compressor

Type

Semi-hermetic Screw

Semi-hermetic Screw

Semi-hermetic Screw

Quantity

1

1

1

Refrigerant

Type

R407C

R407C

R407C

Fan

Type

Low-noise Axial Flow

Low-noise Axial Flow

Low-noise Axial Flow

Quantity

2

4

6

Water-side Heat Exchanger

Flow Rate

17.2 m³/h

32.6 m³/h

39.3 m³/h

Pressure Drop

45Kpa

45Kpa

46Kpa

Connection Size

Φ76×4

Φ89×5

Φ114×5

Dimensions & weight

Length

1450mm

2300mm

2300mm

Width

2240mm

2140mm

2140mm

Height

2310mm

2410mm

2410mm

Weight

1250Kg

2040Kg

3310Kg

Operating Weight  

1310Kg

2100Kg

3380Kg

Explosion-proof Marking

Explosion-proof Marking

Ex d ib mb IIB T4 Gb

Ex d ib mb IIB T4 Gb

Ex d ib mb IIB T4 Gb

FAQ
A:

CNWINNEX explosion-proof systems are widely deployed in oil & gas, petrochemicals, pharmaceuticals, ports & terminals, mining, power generation, offshore platforms, and other areas where flammable gases or dusts are present. Typical applications include control room climate control, hazardous area logistics and access management, video surveillance & security, pressurized analyzer shelters, robotic inspection, as well as custom explosion-proof enclosures and system integration.

A:

An explosion-proof air conditioner is a specialized HVAC unit designed for hazardous environments where flammable gases, vapors, or combustible dusts are present (e.g., petrochemical plants, gas stations, paint booths, pharmaceutical labs).

The most critical difference from a standard air conditioner lies in “active ignition prevention.” Standard units generate tiny sparks during normal operation – such as when relays open/close, compressors start/stop, or circuits make/break. While safe in normal air, these sparks can be deadly in an explosive atmosphere.

A:

CNWINNEX’s explosion-proof design is based on the T4 temperature class. For high-temperature regions such as the Middle East or areas with extreme summer heat, we offer custom units rated for ambient temperatures up to 60°C (140°F) , ensuring reliable operation without overload in harsh tropical climates. For cold regions, we offer custom units rated for ambient temperatures as low as -50°C (-58°F) , guaranteeing safe operation in extreme arctic conditions.

A:

The explosion-proof rating of CNWINNEX air conditioners is:
Ex 2 G D Ex db ib mb IIB T4 Gb / Ex 2 G D Ex db ib mb IIC T4 Gb / Ex ib mb tb IIIC T130°C Db
●For Gas (G): Ex db ib mb IIC T4 Gb
Suitable for IIC gas groups (including hydrogen, acetylene, etc.), using flameproof (db), intrinsic safety (ib), and encapsulated (mb) combined protection. Temperature class T4 (max surface temperature ≤135°C), Equipment Protection Level Gb.
●For Dust (D): Ex ib mb tb IIIC T130°C Db
Suitable for IIIC conductive dusts, using intrinsic safety (ib), encapsulation (mb), and dust-tight (tb) protection. Maximum surface temperature 130°C, Equipment Protection Level Db.

A:

CNWINNEX products comply with international explosion-proof certification standards such as ISO, CNEX, ATEX, IECEx, SAA, EAC, ensuring safe use in different countries and regions., and BV or DNV (for offshore applications) . Depending on the product type and zone classification, we offer various protection concepts including Ex d, Ex e, Ex ib, and Ex nA, with ingress protection up to IP66/IP67, ensuring safe and compliant operation in hazardous environments worldwide.

A:

Absolutely. Explosion-proof Custom Engineering is our sixth core business. From non-standard Ex components (special material junction boxes, intrinsically safe sensors, etc.) to integrated Ex systems (skid-mounted control rooms, pressurized cabins, legacy equipment retrofitting), we provide full-process custom services covering conceptual design, 3D simulation, compliance certification, manufacturing, and delivery. Simply share your operating parameters and functional needs, and we will engineer a dedicated explosion-proof safety solution for you.

Related
Message
SUBMIT